Monday, October 28, 2019

Absorption System and How it Works By Mohammad Imran

 Absorption System and How it Works? By Mohammad Imran 






1) Condenser: Just like in the traditional condenser of the vapor compression cycle, the refrigerant enters the condenser at high pressure and temperature and gets condensed. The condenser is of water cooled type.
2) Expansion valve or restriction: When the refrigerant passes through the expansion valve, its pressure and temperature reduces suddenly. This refrigerant (ammonia in this case) then enters the evaporator.
3) Evaporator: The refrigerant at very low pressure and temperature enters the evaporator and produces the cooling effect. In the vapor compression cycle this refrigerant is sucked by the compressor, but in the vapor absorption cycle, this refrigerant flows to the absorber that acts as the suction part of the refrigeration cycle.
4) Absorber: The absorber is a sort of vessel consisting of water that acts as the absorbent, and the previous absorbed refrigerant. Thus the absorber consists of the weak solution of the refrigerant (ammonia in this case) and absorbent (water in this case). When ammonia from the evaporator enters the absorber, it is absorbed by the absorbent due to which the pressure inside the absorber reduces further leading to more flow of the refrigerant from the evaporator to the absorber. At high temperature water absorbs lesser ammonia, hence it is cooled by the external coolant to increase it ammonia absorption capacity.

Wednesday, October 23, 2019

The Burj Khalifa by Mohammad Imran

The Burj Khalifa construction details by Mohammad Imran.











 known as the Burj Dubai prior to its inauguration in 2010, is a skyscraper in Dubai, United Arab Emirates. With a total height of 829.8 m and a roof height of 828 m, the Burj Khalifa has been the tallest structure and building in the world since its topping out in 2009. 

ahisr.blogspot.com



https://www.youtube.com/channel/UCej-mX5F6GqsPlhhHrQC4Nw


Thursday, October 10, 2019

Thermostatic Expansion Valve by Mohammad Imran.

Pressures Acting Inside the Thermostatic Expansion Valve by Mohammad Imran.


or TEV. The working of the thermostatic expansion valve can be explained with the help of the attached image of the valve. ... The pressure P2 is the pressure acting on the lower side of the diaphragm due to the refrigerant pressure inside the evaporator.

https://ahisr.blogspot.com/?m=1

Sunday, October 6, 2019

Personal protective Equipment (PPE) ! Mohammad Imran


Personal protective Equipment (PPE) ! Mohammad Imran





https://ahisr.blogspot.com/2019/07/energy-efficiency-ratio-eer-by-imran.html?m=1

Monday, September 30, 2019

Refrigerant R-32,R-134a, R-410A, R-22 ! Imran



Mathematics symbols! Imran


Mathematics common Symbols ! Imran


Sunday, September 29, 2019

Link Aadhaar Card to Voter ID EPIC through SMS ! Imran


Link Aadhaar Card to Voter ID EPIC through SMS. By Mohammad Imran



Because there has no way to find on the official website. Only you can link your voter id with Aadhar.

Send an SMS from your registered mobile number.

The SMS has to be sent to 166 or 51969.

The format of the message is ECILINK <SPACE><EPIC No.>< SPACE><Aadhaar No.>

Monday, September 16, 2019

The Top 08 causes of high humidity in your home!Imran

The Top 08 causes of high humidity in your home by Mohammad Imran.
  • Showering. Bathrooms are often humid places and moisture is released into the air by something as simple as taking a shower. ...
  • Boiling a kettle or cooking. ...
  • Drying laundry inside. ...
  • Gas heaters / propane heaters. ...
  • Poor ventilation. ...
  • Rising damp. ...
  • Renovations. ...
  • Coastal air.

Monday, September 9, 2019

Difference between AHU & FCU BY Mohammad Imran


Difference  between AHU & FCU By Mohammad  Imran




1. AHU is generally a bigger system than FCU.

2. AHU is more complex than the FCU and that AHU are often used in bigger establishments or spaces.

3. The AHU system usually channels air through ducts whereas the FCU don’t have any ductworks.

4. AHU system treats outside air while FCUs basically recycle or re-circulates the air.

5. AHU have sections for reheating and humidifying whereas the FCU does not have any.

6. FCU are often observed to be noisier than the AHU

Sunday, September 8, 2019

Here are 8 things you can do to build up your self-confidence !Mohammad Imran


Featured snippet from the we

Here are 8 things you can do to build up your self-confidence by Mohammad  Imran 


  1. Visualize yourself as you want to be. ...
  2. Affirm yourself. ...
  3. Do one thing that scares you every day. ...
  4. Question your inner critic. ...
  5. Take the 100 days of rejection challenge. ...
  6. Set yourself up to win. ...
  7. Help someone else. ...
  8. Care for yourself

Friday, September 6, 2019

Avoid the 5 Common HVAC Installation Mistakes ! Imran

Avoid the 5 Common HVAC Installation MistakesChoosing the Wrong Installer. One of the first mistakes homeowners or businesses make is hiring the wrong HVAC contractor By.
                                              MOHAMMAD IMRAN 



  • Selecting the Wrong Size. ...
  • Poor Air Distribution Design. ...
  • Poorly Designed Drain Systems.
  • Incorrect Exhaust.

Friday, August 30, 2019

The Perfect Way to Introduce Yourself @ interview ! Imran



The Perfect Way to Introduce Yourself by Mohammad Imran .


GOOD Morning Sir/ Madam 





First of all I would like to thank you, for giving me an opportunity to introduce my self.

My self Name I belong from New Delhi.

I am pursuing my under graduation in Information Technology from Institute of Technology  .

I did my Intermediate from State Board with 72% & High school from State Board with 75%.

I like computer, Because In my schooling days, I have scored High marks in that subject compared to Maths, physics.

My Hobbies is playing shuttle, A Passion for music and teaching kids.

My Strength is takes Initiative to work independently, Good leadership skill, Adaptable to any kind of situation in estranged group & Helping tendency.

My Weakness is I am not comfortable, until I finish my work in the given time & over friendly in nature.

My Short term goal is to get the job in reputed company.

My Long term goal is to become more responsible and knowledgeable personality and on respectable position on my company.

That's all about me!

Thank you very much for giving a great opportunity to introduce my self behind you.



Thanks 

Thursday, August 29, 2019

Which chemical is used to clean chimney & how to clean !Imran?

Which chemical is used to clean chimney & how to clean? By Imran









  1. Remove the filters from the chimney.
  2. Fill a bucket with boiling water.
  3. Put 3 tablespoons of baking soda and salt and 2 cups of vinegar in boiling water.
  4. Soak the filters in it for 1 to 2 hours.
  5. Scrub with the scrub brush.
  6. Clean it with water. And put the filters back in their place.

Saturday, August 24, 2019

How to Eliminate Microbial Growth in HVAC ! Imran


Microbial growth in your HVAC system can reduce energy efficiency and contaminate the air in your building. This is a particular risk in hot, humid areas like Houston and along the Texas coast, but it can occur in buildings anywhere. Inside the HVAC system it is often cold, dark, and wet—providing the perfect environment for mold and other microbial organisms to grow.
How you clean and maintain your evaporator coils, and even the filter you use can affect the spread of bacteria, viruses, mildew, and mold in your system. Here are some tips to help eliminate or prevent microbial growth in your HVAC.

Keep Your Coils and Whole System Clean
Routine preventive maintenance is essential for maintaining the cleanliness and efficiency of your air handlers. Heat transfer across the coils is critical to energy efficiency. When there is a buildup of biofilm or other grime on the coils, it will reduce the unit’s efficiency and require more energy to heat and cool the building. This type of growth also harms air quality in the building, especially when it occurs downstream from the filters. Any spores or particles released into the airstream below the filters will go directly into the air you breathe.
Regular HVAC coil cleaning (at least once per year) helps prevent both microbial growth and the buildup of other contaminants that can negatively affect your HVAC system. For example, steam cleaning is effective because it uses heat to kill growth on the evaporator coils.
It’s also important to remember the drain pan under the coils. Condensation and runoff collect under the unit and need to be captured and drained out of the system, but if there is any standing water or residue, it needs to be treated. HVAC pan tablets can be applied based on the tonnage of the unit to prevent algae or other organisms from growing in this area. Without proper treatment, the drain pan can become clogged—potentially leading to spillage that can damage your system and cause microbial growth to spread.

Friday, August 23, 2019

Pure water can't conduct electricity ! Imran

Pure water can't conduct electricity
             By Mohammad Imran.



 because it does not contain ions. Because of diluting pure water with acid or a base or a salt, because they produce ions due to the dilution. Pure water does not conduct electricity.Only water can conduct electricity because it has some minerals present in it.

Cause of fire & how to prevent from fire in Air condition ! Imran

Causes



Most air conditioning fires are caused by a short circuit in the wiring that causes the appliance to overheat and subsequently ignite. Frequent power surges or fluctuation in the amount of voltage the air conditioner receives can also overheat the unit.

Considerations

Portable air conditioning units are a greater fire risk than stationary units or central air. These units are typically smaller than their permanent counterparts – making it more difficult for the unit to keep up with cooling demands. The longer the air conditioner runs, the more likely it is to overheat or suffer a mechanical failure that ultimately causes a fire.

Prevention

Routinely maintaining your air conditioning unit and having it inspected at least every 4 months will help you catch problems with the unit before those problems result in a house fire.

Thursday, August 22, 2019

How volume control Dampers (VCD) is worked !Imran

The Volume Control Damper is used to control air flow in air duct. By Mohammad Imran.
                    





This unit comes with complete manual quadrant or motorized actuators. Volume Control Dampers can be manufactured with galvanized steel, stainless steel and aluminum and are suitable for the systems requiring air control. It would be easy to choose if you have a sound knowledge of the features of volume control damper. Often, the main consideration in choosing a volume damper is its size and the size of the area where it is to be located. Before searching for the perfect damper, find time to measure the room where you intend to place it


Centrifugal Pump troubleshooting ! Imran

Pump troubleshooting by Mohammad Imran

SUBJECT: The pump works for a while and then loses suction 10-12




A couple of things you must keep in mind when troubleshooting centrifugal pump problems:
  • The centrifugal pump always pumps the difference between the suction and discharge heads. If the suction head increases, the pump head will decrease to meet the system requirements. If the suction head decreases the pump head will increase to meet the system requirements.
  • A centrifugal pump always pumps a combination of head and capacity. These two numbers multiplied together must remain a constant. In other words, if the head increases the capacity must decrease. Likewise if the head decreases, the capacity must increase.
  • The pump will pump where the pump curve intersects the system curve.
  • If the pump is not meeting the system curve requirements the problem could be in the pump, the suction side including the piping and source tank, or somewhere in the discharge system.
  • Most pumps are oversized because of safety factors that were added at the time the pump was sized. This means that throttling is a normal condition in most plants, causing the pump to run on the left hand side of its curve.

Monday, August 19, 2019

Impact of Low Refrigerant ! Imran

Low refrigerant



flow will also cause refrigerant-cooled compressors to overheat. Low evaporator pressure: Low evaporator pressure is caused by the compressor being starved of refrigerant. ... This lower temperature will cause a lower pressure in the condenser because of the pressure-temperature relationship at saturation.

Friday, August 2, 2019

How to replace an AC capacitor!by Imran

How to Replace an AC Capacitor


You can purchase a replacement at a hardware store. Then, it’s time to install:
1. Shut off the power to your air conditioning system at the breaker panel
2. Unscrew the side panel of your condenser unit to access the capacitor. 3. Locate the capacitor and discharge the power
4. Dismount the old capacitor and note how the wires are connected
5. Disconnect the wires carefully from the three capacitor connectors, labeled HERM, Fan, and C. Make a note or take a picture of which colored wires connect to which connector for later reference.
6. Install the new capacitor according to the manual
7. Screw the side panel back on the condenser unit.

Symptoms of bad AC Capacitor!By Imran

Symptoms of a Bad AC Capacitor.


If your air conditioner is not blowing cold air, a bad capacitor may be the reason.
However, look for the simple solutions first: Maybe you need to change the air filters, or it could be one of several other reasons.
Once you rule them out, if your unit is still blowing warm air, the issue may be the capacitor.
The most common signs and symptoms of a bad AC capacitor include:

AC not blowing cold air

AC takes a while to start once you turn it on

Humming sound coming from your air conditioner

AC shuts off on its own

AC won’t turn on

Monday, July 29, 2019

Diabetic common symptoms!By Imran

  Diabetic women and men have in common symptoms 



  • Excessive thirst and hunger. D
  • Frequent urination (from urinary tract infections or kidney problems)
  • Weight loss or gain.
  • Fatigue.
  • Irritability.
  • Blurred vision.
  • Slow-healing wounds.
  • Nausea.

Friday, July 26, 2019

Symptoms of kidney stone ! By Imran

Here are eight signs and symptoms that you may have kidney stones.
Pain in the back, belly, or side. ... Pain or burning during urination. ... Urgent need to go. ... Blood in the urine. ... Cloudy or smelly urine. ... Going a small amount at a time. ... Nausea and vomiting. ... Fever and chills

Tuesday, July 23, 2019

How to Prepare for an Interview !By Imran

How to Prepare for an Interview: The Ultimate Guide.
Before your interview, spend some real time on the employer's website. Dig into the job description. ... Write down the questions you're likely to be asked, and practice saying your answers out loud. Figure out what you're most nervous about being asked. Come up with questions of your own to ask.

Monday, July 22, 2019

Some common symptoms of enlarge Spleen! By Imran

enlarged spleen
No symptoms in some cases. Pain or fullness in the left upper abdomen that may spread to the left shoulder. Feeling full without eating or after eating only a small amount from the enlarged spleen pressing on your stomach. Anemia. Fatigue. Frequent infections. Easy bleeding

LG error code troubleshooting!By Imran

LG Error Code troubleshooting
.

Acute pancreatitis signs and symptoms! By Imran

Acute pancreatitis signs and symptoms
Upper abdominal pain. Abdominal pain that radiates to your back. Abdominal pain that feels worse after eating. Fever. Rapid pulse. Nausea. Vomiting. Tenderness when touching the abdomen.

Sunday, July 21, 2019

Common heart attack signs & Symptoms! By Imran

Common heart attack signs and symptoms
Pressure, tightness, pain, or a squeezing or aching sensation in your chest or arms that may spread to your neck, jaw or back. Nausea, indigestion, heartburn or abdominal pain. Shortness of breath. Cold sweat. Fatigue. Lightheadedness or sudden dizziness. Thanks for read this topic subscribe for new updates.

How to get Adsense account approval !By Imran

How to get Adsense account approval for BlogSpot blog:

Buy a custom domain name.


Use Google apps to create a professional email address.


Add pages like About, Contact.


Ensure you use a clean BlogSpot design.


Have at least 10-15 well-written blog posts.


Ensure you don't use copyright images.


Drain line blockage troubleshooting !By Imran

Blockages in the AC Drain Line
1. Turn HVAC system off. 2. Locate cleaning port. If the unit has turned off due to a blockage, you may need a bucket to collect the condensation resting in the drain pan. 3. Remove cleaning port cap. 4. Assess clog. If you can see the blockage, attempt to remove the blockage. Do not push it further away. Instead, attempt to lift the blockage out of the drain pipe. If the blockage breaks, separates and falls down the pipe do not be alarmed. It can be rinsed out with water. 5. Slowly pour cleaning solution down PVC drain line. If cleaning solution fills drain line, do not continue to pour solution. Follow steps in Method 2. 6. After pouring is complete, assess the blockage. If the cleaning solution does not flow out of the drain line, the blockage is still intact. This may be a sign that there is a larger block in the drain line. Follow steps in Method 2. If the pipe fills and slowly drains then repeat step 5 until cleaning solution passes without difficulty. 7. Replace cleaning port cap. 8. Turn system back on.

Rankine cycle! By Imran

Rankine cycle By Mohammad Imran
The Rankine cycle is a model used to predict the performance of steam turbine systems. It was also used to study the performance of reciprocating steam engines. The Rankine cycle is an idealized thermodynamic cycle of a heat engine that converts heat into mechanical work while undergoing phase change.

Advantages and Disadvantages of Thermal Power Plant! By Imran

Advantages and Disadvantages of Thermal Power Plant:
Advantages: Low setup and maintenance cost. It is not directly related to climate condition like hydro power plant. Large amount of coal available at earth. Easy maintenance. Less land area required. It can be installed near load center which minimize transmission losses. It can be installed near coal mines which can minimize transportation cost of fuel. Disadvantages: Low cyclic efficiency around 35 to 45 percent. It continuously generates smoke which contributes in increase air pollution. It uses consumable fuel. Operation cost is high compare to hydro and nuclear power plant. It creates large amount of ash per hour so ash handling is quiet difficult. Sometimes heated water directly drawn into river which can harm life cycle of water living.

Saturday, July 20, 2019

Ohm's Power Law Equation ! By Imran

Ohm's Power law equation.
Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

Ohm's low in triangle form!By Imran

Ohm's Law Ohm's law shows a linear relationship between the voltage and the current in an electrical circuit.
The resistor's voltage drop and resistance set the DC current flow through the resistor. With water flow analogy we can imagine the electric current as water current through pipe, the resistor as a thin pipe that limits the water flow, the voltage as height difference of the water that enables the water flow. Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

Chiller routine PPM!By Imran

Chillers often represent a plant's single largest electric load. But factor in fouled tubes, leaking refrigerant, or myriad other factors, and operating costs can quickly escalate by eight to 10%. Operating chillers at their peak performance will save energy and maintenance costs.
Chiller maintenance has advanced significantly, due to new developments in centrifugal chillers with magnetic bearing chillers, and new remote monitoring technologies. As a result of remote monitoring, the industry has been moving toward demand maintenance programs and away from pre-determined schedule maintenance. Whichever program you use, here are 10 maintenance tips that apply to most centrifugal chillers, to help maintain high efficiency: Keep a daily log The daily log is still the first step toward maintaining an efficiently-run chiller plant. The log allows you to build a history of operating conditions including temperatures, pressures, fluid levels, and flow rates. Remote monitoring technologies allow you to inspect machines continually rather than monthly or every other month. And, it allows you to easily generate trend reports that help to identify maintenance needs before they become an issue. Keep tubes clean for efficient heat transfer Heat transfer efficiency has the greatest single effect on chiller performance, so clean heat transfer is fundamental to maintaining high efficiency. Contaminants such as minerals, scale, mud, algae and other impurities increase thermal resistance and reduce overall performance. Approach temperatures are a good indicator of heat transfer efficiency. Higher approach temperatures are prime indicators that heat transfer efficiency is decreasing. Condenser tubes should be brush cleaned at least annually, or per your demand maintenance schedule to keep them free of contaminants. Treat condenser water to prevent scale, corrosion All condenser water loops using open cooling sources (such as atmospheric cooling towers) require water treatment of some sort to eliminate scale, corrosion and biological growth. All lead to fouling in the condensers and impede heat transfer and can decrease tube and piping effectiveness. Inspect chilled water loops once a year or regularly with remote monitoring for general water quality and evidence of corrosion. Lower entering water temperature Lowering the temperature of the entering condenser water will improve the chiller's efficiency. On some building systems, the operator will lower the chilled water set point to overcome air handler deficiencies such as dirty coils. This cures the symptom but not the problem, and makes the chiller work harder for the same net cooling effect. Keep chilled water flow rate between 3 to 12-ft per second Changing the chilled water flow rate affects a chiller's performance. Too low a flow rate lowers the chiller efficiency and ultimately leads to laminar flow. The minimum flow rate is typically around 3-ft. per second (FPS). Too high a flow rate leads to vibration, noise, and tube erosion. The maximum recommended flow rate is typically around 12 FPS. Maintain adequate refrigerant charge The actual amount of cooling a chiller provides depends on how much refrigerant it moves through the compressor. It is important to maintain the proper level of refrigerant for the conditions desired. Refrigerant leaks, as well as air and moisture introduced into the system, will decrease efficiency and the reliability of the system. A low refrigerant charge will cause the compressor to work harder for less cooling effect. Prevent inefficiencies caused by non-condensables Non-condensables such as air and moisture leak into low pressure chillers because their evaporators operate in a vacuum. Non-condensables can lower the real efficiency of the chiller from the rated performance by as much as 4% at 60% load and 7% at 100% load. Purge units minimize the effect of non-condensables. Analyze compressor oil Send a sample of the lubrication oil to a laboratory for a “spectrometric” chemical analysis once a year. Like any hermetically sealed refrigeration system, the oil should only be replaced if the analysis indicates it's needed. High moisture can indicate a problem with the purge unit. Sample low pressure chillers more frequently, based on purge run hours. Check oil filters for pressure drop and replace them if the oil charge is replaced. New, magnetic bearing frictionless chillers require distinctly different maintenance and operations from traditional centrifugal chillers. Oil has been eliminated in the design of these chiller systems, further reducing maintenance costs. Check operation of starters and motors For efficient operation of starters and motors, check the safety and sensor calibrations on microprocessor controls (consult manufacturer's guidelines). Then, check electrical connections, wiring, and switchgear related to the chiller for hot spots and worn contacts. To prevent insulation faults, test electrical motor windings for insulation resistance to ground and winding-to-winding. Check the shaft seal of open drive motors for possible refrigerant leaks, and clean motor cooling air vents to ensure maximum cooling effect. Install variable speed drives The chiller motor is typically the largest single electrical load in a building. With the right operating conditions, variable speed drives (VSD) can offer significant energy savings. Varying motor speed matches motor efficiency to load and wastes less energy. Variable speed drives also act as a soft starter to lower the inrush current for the motor to almost that of the full load running amps. This is an important factor for chillers operating on emergency power generators. Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

Wind Power Plant Working Principle!By Imran.

Wind Power Plant Working principle By Mohammad Imran HVAC engineer. Wind energy is an indirect form of solar energy since wind is produced chiefly by the uneven heating of the earth’s crust by the sun. The kinetic energy of the wind can be utilized to produce with the help of wind turbine.
Wind Power Plant Working Principle As the free wind stream interacts with turbine rotor, it transfers a part of the kinetic energy to the rotor due to which its speed decreases. This difference in kinetic energy is converted into mechanical power. This is the basic wind power plant working principle. The total wind power is equal to the incoming kinetic energy of the wind stream. It can be expressed as: Total wind power, Pt = (ρACi3)/2 Where, ρ = density of air (in kg/m3) A = rotor swept area = πr2 (r = radius of blades in meters) Ci = incoming wind velocity (in m/s). The density of air (ρ) is somewhat complicated since it depends on the definition of “ideal” air, the temperature, the altitude, and the water vapor content. It is approximately 1.2 kg/m3 at sea level and room temperature. Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

Friday, July 19, 2019

Energy Efficiency Ratio EER !By Imran

Energy Efficiency Ratio EER The Energy Efficiency Ratio - EER - is a term generally used to define cooling energy efficiency of unitary air-conditioning and heat pump system.
The efficiency is determined at a single rated condition specified by an appropriate equipment standard and is defined as the ratio of net cooling capacity - or heat removed in Btu - to the total input rate of electric energy applied - in Wh. The units of EER are Btu/Wh. EER = Qc / E (3) where EER = energy efficient ratio (Btu/Wh) Qc = net cooling energy (Btu) E = applied electrical energy (Wh) This efficiency term typically includes the energy requirement of auxiliary systems such as the indoor and outdoor fans. higher EER - more efficient system Example - EER for an Air Conditioner Unit The heat removed and electrical power consumed for the air conditioner unit can be measured and calculated in different ways. One simple alternative is to calculate mean values from some . The heat removed for 3 hours can be estimated to Qc = ((8500 Btu/h + 10000 Btu/h + 7000 Btu/h) / 3) (3 h) = 25500 Btu The electrical consumption for 3 hours can be estimated to E = ((600 W + 700 W + 550 W) / 3) (3 h) = 1850 Wh EER for the air conditioner unit can be estimated to EER = (25500 Btu) / (1850 Wh) = 13.8 Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

How to calculate Duct Air Flow in CFM with help of Pressure Sensor ! By Imran

Determining Duct Air Flow in CFM using to Pressure Sensor by Imran
To calculate Air Flow in Cubic Feet per Minute (CFM), determine the Flow Velocity in feet per minute, then multiply this figure by the Duct Cross Sectional Area. Air Flow in CFM (Q) = Flow Velocity in Feet Per Minute (V) x Duct Cross Sectional Area (A) Determining Flow Velocity The easiest way to determine Flow Velocity is to measure the Velocity Pressure in the duct with a Pitot Tube Assembly connected to a differential pressure sensor. The Pitot Tube Assembly includes a Static Pressure Probe and a Total Pressure Probe. A Total Pressure Probe, aligned into the airflow, senses the duct velocity pressure and the static pressure, which equals the total pressure. A Static Pressure Probe aligned at a right angle to the airflow senses only the static pressure. The difference between the total pressure reading and the static pressure reading is the Velocity Pressure. If you connect the Total Pressure Probe to the HIGH port on a differential pressure sensor and the Static Pressure Probe to the LOW port on the differential pressure sensor, then the sensor’s output will be the Velocity Pressure, as shown in the figures below. Fig. 1: BAPI Pitot Tube Assembly, includes Static and Total Pressure Probe Assemblies (ZPS-ACC12) Fig. 2: BAPI Differential Zone Pressure Sensor (ZPS) measuring Velocity Pressure The Flow Velocity is then determined with the following equation: V = 4005 x √ΔP V = Flow Velocity in feet per minute. √= Square root of the number to the right . ΔP = The Velocity Pressure measured by the pressure sensor Example: Measuring a Velocity Pressure of .75” W.C. equals a Flow Velocity of 3,468 Ft/Min. V = 4005 x √0.75 √0.75 = 0.866 • 4005 x 0.866 = 3,468 • Flow Velocity = 3,468 Ft/Min Determining Duct Cross Sectional Area After obtaining the Flow Velocity from the previous procedure, that figure is now multiplied by the Duct Cross Sectional Area to determine the Air Flow in CFM. There are two different equations for determining the Duct Cross Sectional Area, one for round ducts and one for square or rectangular ducts. The equation for square or rectangular ducts is: A = X x Y A = Duct Cross Sectional Area X = Duct height in feet Y = Duct width in feet. The equation for a round duct is: A = π x r² A = Duct Cross Sectional Area π= 3.14159 r = radius of duct in feet Example: An 18” diameter round duct has a Duct Cross Sectional Area of 1.77 Ft² A = π x r² or A = 3.14158 x .5625 18” diameter is 1.5 feet, therefore the radius is .75 feet • r² = 0.75² = 0.5265 • π = 3.14159 A = 3.14159 x 0.5625 = 1.77 Ft² Determining Air Flow in CFM After obtaining the Flow Velocity and the Duct Cross Sectional Area from the previous two procedures, the Air Flow in CFM is determined by multiplying the two: Air Flow in CFM (Q) = Flow Velocity in Feet Per Minute (V) x Duct Cross Sectional Area (A) Example: An 18” diameter round duct with a Velocity Pressure of .75” W.C. has an Air Flow of 6,128 CFM The Flow Velocity is 3,468 Ft/Min. V = 4005 x √ΔP) V = 4005 x √0.75) √0.75 = 0.866 • 4005 x 0.866 = 3,468 • Flow Velocity = 3,468 Ft/Min The Duct Cross Sectional Area is 1.77 Ft² A = π x r² π= 3.14159 • r² = 0.75² = 0.5625 Duct Cross Sectional Area (A) = 3.14159 x 0.5625 = 1.77 Ft² The Air Flow in CFM is 6,128 Ft³/Min Air Flow in CFM (Q) = Flow Velocity in Feet Per Minute (V) x Duct Cross Sectional Area (A) Air Flow in CFM (Q) = 3,468 Ft/Min x 1.77 Ft² = 6,128 CFM. Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

Chiller Chemical dosing system water treatment! By Imran

Chemical treatment (or dosing):
Proprietary (like NALCOOL) or generic chemicals (like Sodium Silicate, Sodium Nitrite, and Sodium Sulfite) compositions are used to prevent the chiller system from corrosion, scaling, fouling and microbiological growth. How? Mainly in three ways: first, these chemicals react with the pipes to form a protective thin inside layer; second, the chemicals help in maintaining the pH level; and third, the chemicals remove corrosive dissolved oxygen in the water. Dosing pumps are used for applying the predetermined quantities of chemicals at regular intervals. Mechanical Treatment: Before commissioning, the whole system should be cleaned and flushed using treated water and commission it as soon as possible. Attend all the leaking points regularly. Filtration: The filter is used for removing (or at least reducing) the solid particles (like welding flush, concrete particles, etc.). UV and Ozone treatment: This method is effective for preventing the microbiological growth in the system, but is not used widely for chillers unless there is some restriction for chemical treatment. Unlike chemical dosing, this treatment does not generate harmful chemical by-products. Thanks for read if you want to anything related to HVAC and Mechanical Engineering then comments and subscribe for new update.

What is (DX )direct expansion air conditioning unit!By Imran

direct expansion air conditioning unit, also called a DX unit, cools indoor air using a condensed refrigerant liquid. It is the type of air conditioning unit most commonly used in homes in the United States.
Direct Expansion Cooling The unit cools air by passing the condensed refrigerant through a heat exchanger inside the building to be cooled. In this part of the unit, called the evaporator, the refrigerant expands as it absorbs heat, eventually converting to a gas. The unit then pumps the refrigerant to a compressor, which compresses the gas and passes it through another heat exchanger, the condenser, outside the building. The heat that has been absorbed by the refrigerant is released to the outdoor air, and the cooled, compressed refrigerant is once again in liquid form. The unit pumps the cooled refrigerant liquid back to the evaporator and the cycle begins again.

Thursday, July 11, 2019

Common Causes of Condenser Fan Motor Overheating !By Imran

Common causes of Condenser Fan Motor Overheating? There are a few likely causes that are to blame when a condenser fan motor overheats. They include:
A bad motor. If this is the cause and the motor is new, check the warranty to see if you can get a replacement at no charge. Incorrectly sized motor. Check the manufacturer’s recommendations for ensuring the right sized motor. Overamping. This can be due to either the wrong start run capacitor being installed, or from an incorrectly sized fan blade. Replacing the capacitor and/or fan blade with the correct one should solve the problem. Poor airflow. Not having the fan blades installed in a correct position can result in a lack of airflow and cause the motor to overheat. Lack of maintenance. If the motor has not been lubricated, or the unit kept clean, this can lead to overheating problems. Condensor Coil fully choked Blockages in side condensor